The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.
Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.
The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.
Inspection # 13448445 | ||
---|---|---|
VIOLATIONS | BUILDING CODE CITATION | VIOLATION DETAILS |
FP1314 | SEC. 13-76-050 MAKE NECESSARY REPAIRS TO COMMUNICATION SYSTEM AND MAINTAIN IN WORKING ORDER AT ALL TIMES. | ENSURE THAT THE ACTUAL STAIRWELL DESIGNATIONS (A & B) ARE REFLECTED ON THE LABELS AND DIGITAL READOUTS OF THE FACP. |
FP1920 | SEC. 15-16-220, 15-16-1110, 15-16-1120, 15-16-400 PROVIDE CLEAR AND UNOBSTRUCTED ACCESS TO ALL SPRINKLER AND/OR STANDPIPE CONTROLS. | KEEP PUMP AREA CLEAR |
FP1928 | SEC. 15-16-220 REPAIR OR REPLACE DEFECTIVE GUARD RAIL. | |
FP1976 | SEC. 15-16-220, 15-16-1170 REPAIR OR REPLACE DEFECTIVE PRESSURE MAINTENANCE PUMP (JOCKEY PUMP). | |
FP2147 | SEC. 15-4-080, 15-4-090, 15-16-310, 15-16-530, 15-16-610, 15-16-800, 15-16-1140, 15-16-1180 PROVIDE MONITORING OF THE FIRE PUMP(S) AT A CONSTANTLY ATTENDED LOCATION. MONITORING SHALL CONSIST OF A PROPERLY LABELLED, SEPARATE AUDIBLE OR VISUAL ALARM FOR PUMP RUNNING, POWER FAILURE, PHASE REVERSAL AND/OR ENGINE FAILURE IN ACCORDANCE WITH NFPA 20--1973 EDITION. | REPAIR NO PUMP RUN OR POWER FAILURE ALARM |
FP2150 | SEC. 15-16-1170 REPAIR AND MAINTAIN THE STANDPIPE SYSTEM AND PLACE IN SERVICE AT ONCE. | provide annual inspection |
FP3117 | SEC.13-76-075,13-196-085, POST ON THE OCCUPANCY SIDE AT EVERY STAIRWELL DOOR INFORMATION INDICATING FLOOR RE-ENTRY LOCATION. | DESIGNATE SCISSOR STAIRWELLS A AND B ON OCCUPANCY SIDE |