The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.

Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.

The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.

ADDRESS: 917 W DAKIN ST
Inspection # 1973708
VIOLATIONS BUILDING CODE CITATION VIOLATION DETAILS
CN010032 Failed to enclose heating plant room by partitions with at least two hour fire resistance. (15-8-210) 1st floor/laundryroom - Hot water heater stored in laundry room - not enclosed; foundation and drywall missing
CN048013 Install foundation under heat producing appliance. (13-180-070) 1st floor/laundryroom - Hot water heater stored in laundry room - not enclosed; foundation and drywall missing
CN061014 Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) South - Exterior wall - Spalling bricks; washed out mortar underneath windows at grade
CN061034 Failed to maintain all interior walls, ceilings and interior woodwork free of flaking, peeling, chipped or loose paint, plaster or structural material. (13-196-540(d), 13-196-641) 3rd floor hallway - Paint bubbling at ceiling
CN065014 Failed to maintain lintel in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North - Lintels - Rusting, warped. (Permit #100664577 issued 8/12/2016 to repair lintels.)
CN066034 Failed to maintain balcony in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North - Balcony rails - Rusting
CN070014 Failed to maintain exterior stairways in safe condition and in sound repair. (13-196-570, 13-196-641) 4th floor south stairwell - Stairs to roof - Spindles spaced 13" to 15" apart, fall hazard; drywall missing down side of stairs - framework exposed - fall hazard
CN073014 Failed to maintain exterior door in sound condition and repair. (13-196-550(d) and (e), 13-196-641) South - Rear double doors - Rubbing ceiling when opened
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) Unit #202 - Water stains on walls near balcony doors; 4th floor North stairwell - Holes in walls (near door); South stairwell - Hole at ceiling (roof level) 2nd floor south stairwell - Cracks in interior masonry wall 3rd floor hallway - Holes at ceiling; paint bubbling; 1st floor lobby - Holes in walls 2nd-4th floor hallways (near elevators) - Cracked plaster; gaps around door frame
CN103015 Failed to maintain floor free from holes and wide cracks and free from loose, warped, protruding or rotting floor boards. (13-196-540(a) and (b)) Unit #202 - Hardwood floors buckling
CN107035 Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) Various hallways and stairwells - Stair and exit signs - Not working at time of inspection
CN190019 Arrange for inspection of premises. (13-12-100) Unable to inspect all apartments and basement (if any). Unverified detectors and conditions.
EL0027 Restore exit and emergency lighting system and related equipment to operable condition. (18-27-700.6) 2nd , 3rd floor hallways - Emergency lights - Not working at time of inspection; 3rd floor hallway - Emergency light - Loose and unsecured; pane cover hanging
EL0029 Remove exposed wiring. (18-27-300.4) 4th floor south stairwell (roof level) - Exposed wires at junction box; fixture or outlet cover missing
NC5042 Failed to provide 1-1/2 hour Class B fire door with self-closing device. (15-8-180) All stairwells - Fire doors - Not fire-rated; tags missing on doors and frames thru-out; 2nd, 3rd floor south stairwell - Fire doors - Loose at hinges; difficult to close - hitting jamb; slow to close
PL157047 Stop leaking water. (18-29-102.3) Unit #202 - Water leaking through balcony doors and down walls; hardwod floors buckling
CN010032 Failed to enclose heating plant room by partitions with at least two hour fire resistance. (15-8-210) 1st floor/laundryroom - Hot water heater stored in laundry room - not enclosed; foundation and drywall missing
CN048013 Install foundation under heat producing appliance. (13-180-070) 1st floor/laundryroom - Hot water heater stored in laundry room - not enclosed; foundation and drywall missing
CN061014 Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) South - Exterior wall - Spalling bricks; washed out mortar underneath windows at grade
CN061034 Failed to maintain all interior walls, ceilings and interior woodwork free of flaking, peeling, chipped or loose paint, plaster or structural material. (13-196-540(d), 13-196-641) 3rd floor hallway - Paint bubbling at ceiling
CN065014 Failed to maintain lintel in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North - Lintels - Rusting, warped. (Permit #100664577 issued 8/12/2016 to repair lintels.)
CN066034 Failed to maintain balcony in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North - Balcony rails - Rusting
CN070014 Failed to maintain exterior stairways in safe condition and in sound repair. (13-196-570, 13-196-641) 4th floor south stairwell - Stairs to roof - Spindles spaced 13" to 15" apart, fall hazard; drywall missing down side of stairs - framework exposed - fall hazard
CN073014 Failed to maintain exterior door in sound condition and repair. (13-196-550(d) and (e), 13-196-641) South - Rear double doors - Rubbing ceiling when opened
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) Unit #202 - Water stains on walls near balcony doors; 4th floor North stairwell - Holes in walls (near door); South stairwell - Hole at ceiling (roof level) 2nd floor south stairwell - Cracks in interior masonry wall 3rd floor hallway - Holes at ceiling; paint bubbling; 1st floor lobby - Holes in walls 2nd-4th floor hallways (near elevators) - Cracked plaster; gaps around door frame
CN103015 Failed to maintain floor free from holes and wide cracks and free from loose, warped, protruding or rotting floor boards. (13-196-540(a) and (b)) Unit #202 - Hardwood floors buckling
CN107035 Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) Various hallways and stairwells - Stair and exit signs - Not working at time of inspection
CN190019 Arrange for inspection of premises. (13-12-100) Unable to inspect all apartments and basement (if any). Unverified detectors and conditions.
EL0027 Restore exit and emergency lighting system and related equipment to operable condition. (18-27-700.6) 2nd , 3rd floor hallways - Emergency lights - Not working at time of inspection; 3rd floor hallway - Emergency light - Loose and unsecured; pane cover hanging
EL0029 Remove exposed wiring. (18-27-300.4) 4th floor south stairwell (roof level) - Exposed wires at junction box; fixture or outlet cover missing
NC5042 Failed to provide 1-1/2 hour Class B fire door with self-closing device. (15-8-180) All stairwells - Fire doors - Not fire-rated; tags missing on doors and frames thru-out; 2nd, 3rd floor south stairwell - Fire doors - Loose at hinges; difficult to close - hitting jamb; slow to close
PL157047 Stop leaking water. (18-29-102.3) Unit #202 - Water leaking through balcony doors and down walls; hardwod floors buckling