The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.
Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.
The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.
Inspection # 10899674 | ||
---|---|---|
VIOLATIONS | BUILDING CODE CITATION | VIOLATION DETAILS |
CN031023 | Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) | Throughout entire building Fire extinguishers with expired (and or missing) tags. |
CN031023 | Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) | Throughout entire building Fire extinguishers with expired (and or missing) tags. |
CN031023 | Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) | Throughout entire building Fire extinguishers with expired (and or missing) tags. |
CN044013 | Failed to fill openings around exposed pipes or power shafting with approved noncombustible materials. (15-8-640) | All floors, all electrical and telecom closets, - Openings around exposed pipes or power shafting shall be filled with approved noncombustible material, or shall be closed off by close-fitting metal caps at the ceiling and floor line, and on each side of a wall, ceiling or partition. As per building code 15-8-640 |
CN044013 | Failed to fill openings around exposed pipes or power shafting with approved noncombustible materials. (15-8-640) | All floors, all electrical and telecom closets, - Openings around exposed pipes or power shafting shall be filled with approved noncombustible material, or shall be closed off by close-fitting metal caps at the ceiling and floor line, and on each side of a wall, ceiling or partition. As per building code 15-8-640 |
CN044013 | Failed to fill openings around exposed pipes or power shafting with approved noncombustible materials. (15-8-640) | All floors, all electrical and telecom closets, - Openings around exposed pipes or power shafting shall be filled with approved noncombustible material, or shall be closed off by close-fitting metal caps at the ceiling and floor line, and on each side of a wall, ceiling or partition. As per building code 15-8-640 |
CN061014 | Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) | Main facade south elevation, stress crack starting at 3rd floor and extend all the way up to parapet. |
CN061014 | Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) | Main facade south elevation, stress crack starting at 3rd floor and extend all the way up to parapet. |
CN061014 | Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) | Main facade south elevation, stress crack starting at 3rd floor and extend all the way up to parapet. |
CN101025 | Failed to maintain interior ceilings and walls reasonably smooth, clean and tight and free from chipped or loose plaster or structural material. (13-196-540(d) and (e)) | South interior entryway walls cracked and broken plaster / drywall sections. |
CN101025 | Failed to maintain interior ceilings and walls reasonably smooth, clean and tight and free from chipped or loose plaster or structural material. (13-196-540(d) and (e)) | South interior entryway walls cracked and broken plaster / drywall sections. |
CN101025 | Failed to maintain interior ceilings and walls reasonably smooth, clean and tight and free from chipped or loose plaster or structural material. (13-196-540(d) and (e)) | South interior entryway walls cracked and broken plaster / drywall sections. |
CN107025 | Failed to install standard internally illuminated exit, fire escape, and/or directional signs. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency exit signs missing or not illuminated. |
CN107025 | Failed to install standard internally illuminated exit, fire escape, and/or directional signs. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency exit signs missing or not illuminated. |
CN107025 | Failed to install standard internally illuminated exit, fire escape, and/or directional signs. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency exit signs missing or not illuminated. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | South interior entryway - exit sign broken. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency lights missing or not working. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency lights missing or not working. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | South interior entryway - exit sign broken. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | Boiler, Gym and laundry rooms, Emergency lights missing or not working. |
CN107035 | Failed to maintain all exit signs illuminated when building is occupied and otherwise maintain exit signs in good condition. (13-196-090, 13-160-700 thru 13-160-770) | South interior entryway - exit sign broken. |
CN190019 | Arrange for inspection of premises. (13-12-100) | Building interior - no response - unverified detectors and conditions . Unable to inspect interior stairways or sides and rear of building. |
CN190019 | Arrange for inspection of premises. (13-12-100) | Building interior - no response - unverified detectors and conditions . Unable to inspect interior stairways or sides and rear of building. |
CN190019 | Arrange for inspection of premises. (13-12-100) | Building interior - no response - unverified detectors and conditions . Unable to inspect interior stairways or sides and rear of building. |
CN197087 | Install carbon monoxide detector within 40 feet of every sleeping room in residential structure. (13-64-190, 13-64-210) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. In a single family residence, be sure the detector is on or below the lowest floor with a place to sleep. In a multiple dwelling residence heated by a boiler, install a detector in the same room as the boiler. Otherwise, each apartment follows single family guidelines. The owner is responsible for installation and written instructions, the tenant for testing, maintenance, and batteries. | Bolier room, missing carbon monoxide detector. |
CN197087 | Install carbon monoxide detector within 40 feet of every sleeping room in residential structure. (13-64-190, 13-64-210) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. In a single family residence, be sure the detector is on or below the lowest floor with a place to sleep. In a multiple dwelling residence heated by a boiler, install a detector in the same room as the boiler. Otherwise, each apartment follows single family guidelines. The owner is responsible for installation and written instructions, the tenant for testing, maintenance, and batteries. | Bolier room, missing carbon monoxide detector. |
CN197087 | Install carbon monoxide detector within 40 feet of every sleeping room in residential structure. (13-64-190, 13-64-210) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. In a single family residence, be sure the detector is on or below the lowest floor with a place to sleep. In a multiple dwelling residence heated by a boiler, install a detector in the same room as the boiler. Otherwise, each apartment follows single family guidelines. The owner is responsible for installation and written instructions, the tenant for testing, maintenance, and batteries. | Bolier room, missing carbon monoxide detector. |
CN198019 | File building registration statement with Building Dept. (13-10-030, 13-10-040) | Building not registered from 2006 through 2013. |
CN198019 | File building registration statement with Building Dept. (13-10-030, 13-10-040) | Building not registered from 2006 through 2013. |
CN198019 | File building registration statement with Building Dept. (13-10-030, 13-10-040) | Building not registered from 2006 through 2013. |
NC2011 | Performed or allowed work to be performed without submitting plans prepared, signed and sealed by a licensed architect or registered structural engineer for approval and without obtaining a permit to perform the work. (13-32-010, 13-32-040, 13-40-020, 13-12-050) | Plans and permit required for all interior renovation, at the time of ninspection several apartments where under construction. |
NC2011 | Performed or allowed work to be performed without submitting plans prepared, signed and sealed by a licensed architect or registered structural engineer for approval and without obtaining a permit to perform the work. (13-32-010, 13-32-040, 13-40-020, 13-12-050) | Plans and permit required for all interior renovation, at the time of ninspection several apartments where under construction. |
NC2011 | Performed or allowed work to be performed without submitting plans prepared, signed and sealed by a licensed architect or registered structural engineer for approval and without obtaining a permit to perform the work. (13-32-010, 13-32-040, 13-40-020, 13-12-050) | Plans and permit required for all interior renovation, at the time of ninspection several apartments where under construction. |
NC5042 | Failed to provide 1-1/2 hour Class B fire door with self-closing device. (15-8-180) | 1st floor boiler room, missing "B" label door |
NC5042 | Failed to provide 1-1/2 hour Class B fire door with self-closing device. (15-8-180) | 1st floor boiler room, missing "B" label door |
NC5042 | Failed to provide 1-1/2 hour Class B fire door with self-closing device. (15-8-180) | 1st floor boiler room, missing "B" label door |
NC6042 | Failed to provide approved self-closing devices on apartment doors opening upon public corridor in residential building over four stories high. (15-8-240(a)(5), 13-196-170) | All floors, all doors, emergency stairwell, west, missing self closers |
NC6042 | Failed to provide approved self-closing devices on apartment doors opening upon public corridor in residential building over four stories high. (15-8-240(a)(5), 13-196-170) | All floors, all doors, emergency stairwell, west, missing self closers |
NC6042 | Failed to provide approved self-closing devices on apartment doors opening upon public corridor in residential building over four stories high. (15-8-240(a)(5), 13-196-170) | All floors, all doors, emergency stairwell, west, missing self closers |
NC6052 | Failed to remove hold-open device preventing operation of self-closing door closure on apartment door. (13-196-170) | Both stairwells, all floors, wood wedge , wires holding open stairwells fire doors. |
NC6052 | Failed to remove hold-open device preventing operation of self-closing door closure on apartment door. (13-196-170) | Both stairwells, all floors, wood wedge , wires holding open stairwells fire doors. |
NC6052 | Failed to remove hold-open device preventing operation of self-closing door closure on apartment door. (13-196-170) | Both stairwells, all floors, wood wedge , wires holding open stairwells fire doors. |