The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.

Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.

The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.

ADDRESS: 739 W BELMONT AVE
Inspection # 10565358
VIOLATIONS BUILDING CODE CITATION VIOLATION DETAILS
CN015062 Failed to remove obstruction from exitway that hampers travel and evacuation. (13-160-070, 13-196-080) South elevation - vehicle parked under fire escape preventing stairs from reaching grade - dangerous and hazardous condition if fire occurs.
CN031013 Failed to install approved fire extinguishers on every floor of residential building more than three stories in height and having floor area exceeding 3,000 square feet. (15-16-160, 15-16-640) 5th floor hall - missing fire extinguisher.
CN031023 Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) Interior of building - fire extinguishers with expired tags (2012).
CN061014 Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) West elevation - concrete beams and columns with exposed rebar, previous repairs are falling off of building, spalling bricks. South elevation - spalling bricks and washed out mortar. Masonry permit required for repairs.
CN061074 Failed to protect public sidewalk or thoroughfare from work done under permit. (13-124-130 thru 13-124-180) Provide canopy for public walkway during repairs to lintels.
CN062024 Failed to maintain parapet wall in good repair and free from cracks and defects. (13-196-530 and 13-196-641) East elevation parapet wall - spalling bricks and washed out mortar.
CN065014 Failed to maintain lintel in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North elevation - rusted and deflecting lintels. Masonry permit required.
CN065024 Failed to maintain projection from wall of building in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) NORTHWEST CORNER 5TH FLOOR, ORNAMENT STONE IS LEANING TOWARD PUBLIC SIDEWALK., PERMIT REQUIRED TO REPAIR.
CN065034 Failed to maintain window sill in good repair and free from cracks and defects. (13-196-530(e), 13-196-550, 13-196-641) West elevation window sills - some with washed out mortar at joint.
CN073014 Failed to maintain exterior door in sound condition and repair. (13-196-550(d) and (e), 13-196-641) 3rd floor fire escape door will not close entirely.
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) unit 506 - 5th floor living room and bathroom ceiling water damaged in living room under windows water damaged wall - holes missing plaster bathroom wall tiles by tub not sealed, 5th floor hall by units 518, 507 wall and ceiling loose and falling plaster water damaged. 4TH FLOOR CORRIDOR, BY UNITS 411 AND 406, CEILING PEELING PAINT.
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) Rear interior stairway ceiling - loose and hanging plaster.
CN104015 Replace broken, missing or defective window panes. (13-196-550 A) West elevation basement windows - broken glass blocks and missing louvered panes.
CN105015 Repair or replace defective door. (13-196-550) 2nd floor south , 1-S stair door rubs.
CN105035 Repair or replace door hardware. (13-196-550) Fire escape doors will not lock shut.
CN106015 Failed to maintain interior stairway system in safe condition and sound repair. (13-196-570) south stair 1st to grade , MISSING HANDRAIL.
CN106015 Failed to maintain interior stairway system in safe condition and sound repair. (13-196-570) Rear stairs at basement - loose handrail.
CN131026 Repair or replace defective screen. (13-196-560 B) ALL ELEVATIONS AND LEVELS, MISSING SEVERAL WINDOW SCREENS.
CN136016 Exterminate roaches and keep dwelling insect-free. (13-196-630 C) basement has roaches.
CN190019 Arrange for inspection of premises. (13-12-100) Interior of Building - Refused entry , unverified detectors and occupancy . Unable to inspect interior stairways and overall condition. Unable to verify complaince of previous violations .
CN197079 Repair or replace defective or out of service smoke detectors and operate continuously. (13-196-130, 13-196-140) Interior of building 5th floor corridor - non working smoke detector.
CN197087 Install carbon monoxide detector within 40 feet of every sleeping room in residential structure. (13-64-190, 13-64-210) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. In a single family residence, be sure the detector is on or below the lowest floor with a place to sleep. In a multiple dwelling residence heated by a boiler, install a detector in the same room as the boiler. Otherwise, each apartment follows single family guidelines. The owner is responsible for installation and written instructions, the tenant for testing, maintenance, and batteries. LAUNDRY ROOM, MISSING CARBON MONOXIDE DETECTOR.
NC5012 Failed to provide stairwell opening with self-closing, framed, 1-1/2 hour Class B door. (15-8-180) All stairway doors - no fire rating tags on doors or jambs.
NC5062 Failed to remove fusible links and/or other hold-open mechanism on stairwell doors in buildings where stairwells serve more than three floors. (15-8-180(c)) All stairway doors are held open with door stops.
CN015062 Failed to remove obstruction from exitway that hampers travel and evacuation. (13-160-070, 13-196-080) South elevation - vehicle parked under fire escape preventing stairs from reaching grade - dangerous and hazardous condition if fire occurs.
CN031013 Failed to install approved fire extinguishers on every floor of residential building more than three stories in height and having floor area exceeding 3,000 square feet. (15-16-160, 15-16-640) 5th floor hall - missing fire extinguisher.
CN031023 Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) Interior of building - fire extinguishers with expired tags (2012).
CN061014 Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) West elevation - concrete beams and columns with exposed rebar, previous repairs are falling off of building, spalling bricks. South elevation - spalling bricks and washed out mortar. Masonry permit required for repairs.
CN061074 Failed to protect public sidewalk or thoroughfare from work done under permit. (13-124-130 thru 13-124-180) Provide canopy for public walkway during repairs to lintels.
CN062024 Failed to maintain parapet wall in good repair and free from cracks and defects. (13-196-530 and 13-196-641) East elevation parapet wall - spalling bricks and washed out mortar.
CN065014 Failed to maintain lintel in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) North elevation - rusted and deflecting lintels. Masonry permit required.
CN065024 Failed to maintain projection from wall of building in good repair and free from cracks and defects. (13-196-530(e), 13-196-641) NORTHWEST CORNER 5TH FLOOR, ORNAMENT STONE IS LEANING TOWARD PUBLIC SIDEWALK., PERMIT REQUIRED TO REPAIR.
CN065034 Failed to maintain window sill in good repair and free from cracks and defects. (13-196-530(e), 13-196-550, 13-196-641) West elevation window sills - some with washed out mortar at joint.
CN073014 Failed to maintain exterior door in sound condition and repair. (13-196-550(d) and (e), 13-196-641) 3rd floor fire escape door will not close entirely.
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) unit 506 - 5th floor living room and bathroom ceiling water damaged in living room under windows water damaged wall - holes missing plaster bathroom wall tiles by tub not sealed, 5th floor hall by units 518, 507 wall and ceiling loose and falling plaster water damaged. 4TH FLOOR CORRIDOR, BY UNITS 411 AND 406, CEILING PEELING PAINT.
CN101015 Failed to maintain interior walls and ceilings free from holes or cracks. (13-19-540(c)) Rear interior stairway ceiling - loose and hanging plaster.
CN104015 Replace broken, missing or defective window panes. (13-196-550 A) West elevation basement windows - broken glass blocks and missing louvered panes.
CN105015 Repair or replace defective door. (13-196-550) 2nd floor south , 1-S stair door rubs.
CN105035 Repair or replace door hardware. (13-196-550) Fire escape doors will not lock shut.
CN106015 Failed to maintain interior stairway system in safe condition and sound repair. (13-196-570) south stair 1st to grade , MISSING HANDRAIL.
CN106015 Failed to maintain interior stairway system in safe condition and sound repair. (13-196-570) Rear stairs at basement - loose handrail.
CN131026 Repair or replace defective screen. (13-196-560 B) ALL ELEVATIONS AND LEVELS, MISSING SEVERAL WINDOW SCREENS.
CN136016 Exterminate roaches and keep dwelling insect-free. (13-196-630 C) basement has roaches.
CN190019 Arrange for inspection of premises. (13-12-100) Interior of Building - Refused entry , unverified detectors and occupancy . Unable to inspect interior stairways and overall condition. Unable to verify complaince of previous violations .
CN197079 Repair or replace defective or out of service smoke detectors and operate continuously. (13-196-130, 13-196-140) Interior of building 5th floor corridor - non working smoke detector.
CN197087 Install carbon monoxide detector within 40 feet of every sleeping room in residential structure. (13-64-190, 13-64-210) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. In a single family residence, be sure the detector is on or below the lowest floor with a place to sleep. In a multiple dwelling residence heated by a boiler, install a detector in the same room as the boiler. Otherwise, each apartment follows single family guidelines. The owner is responsible for installation and written instructions, the tenant for testing, maintenance, and batteries. LAUNDRY ROOM, MISSING CARBON MONOXIDE DETECTOR.
NC5012 Failed to provide stairwell opening with self-closing, framed, 1-1/2 hour Class B door. (15-8-180) All stairway doors - no fire rating tags on doors or jambs.
NC5062 Failed to remove fusible links and/or other hold-open mechanism on stairwell doors in buildings where stairwells serve more than three floors. (15-8-180(c)) All stairway doors are held open with door stops.