The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.
Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.
The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.
Inspection # 1516082 | ||
---|---|---|
VIOLATIONS | BUILDING CODE CITATION | VIOLATION DETAILS |
CN011012 | Failed to provide self-closing, framed, 1-1/2 hour Class B fire door or other approved opening protective assembly for heating plant and/or boiler room. (15-8-230) | 4609 RESTAURANT FURNACE ROOM INSTALL CLASS "B" FIRE DOOR FRAME AND CLOSER |
CN012012 | Failed to construct floor over basement of at least 1/2 hour fire resistance in building built prior to July 8, 1957 containing three or more dwelling units. (13-196-710) | SOUTH EAST BASEMENT PROVIDE 1/2 HOUR CEILING |
CN015062 | Failed to remove obstruction from exitway that hampers travel and evacuation. (13-160-070, 13-196-080) | 4601 RESTAURANT MAINTAIN 36" AISLE THROUGH KITCHEN 36" WIDE TO REAR EXIT DOOR |
CN039013 | Failed to post in a conspicuous location, the approved occupancy card indicating the number of people who may legally occupy such rooms and space in every theater, public assembly unit or open air assembly unit and in every room or portion of such units. (13-84-410) | 4603 RESTAURANT HAS PREVIOUS TENANTS OCCUPANCY CARD & SUBMIT DIAGRAM AND OBTAIN NEW OCCUPANCY CARD |
CN039023 | Failed to post floor plan of every seat and every exit, drawn to 1/8 inch scale, in a conspicuous place outside box office of theater. (15-4-850) | SUBMIT DIAGRAM AND OBTAIN OCCUPANCY CARD |
CN040053 | Failed to obtain frontage consent from adjoining property owner within 150 square feet of lot line for installation of tank for storage of flammable liquids. (13-44-080) | 4601 RESTAURANT FURNACE ROOM STOP LIQUOR STORAGE |
CN074024 | Failed to provide porch which is more than two risers high with rails not less than three and one-half feet above the floor of the porch. (13-196-570(b), 13-196-641 | AT CURRENCY EXCHANGE, GUARDRAIL NEEDED AT REAR TO PROTECT AGAINST ACCIDENTAL FALL OFF INTO STAIRWELL GRADE TO BASEMENT |
CN105055 | Failed to install door viewing device at the entrance door of a dwelling unit. (13-164-030) | APARTMENT ENTRY DOORS PROVIDE VIEWING DEVICES 2ND & 3RD FLOORS 9 MISSING |
CN106015 | Failed to maintain interior stairway system in safe condition and sound repair. (13-196-570) | WOOD STAIRWAY GRADE TO BASEMENT AT CURRENCY EXCHANGE IS DILAPIDATED |
CN107025 | Failed to install standard internally illuminated exit, fire escape, and/or directional signs. (13-196-090, 13-160-700 thru 13-160-770) | INSTALL DIRECTIONAL SIGN IN KITCHEN SHOWING REAR EGRESS DOOR |
CN138056 | Remove accumulation of refuse and debris and keep premises clean. (13-196-580, 13-196-630) | BASEMENT BELOW CURRENCEY EXCHANGE WITH CLUTTER (BOXES OF RECORDS)JUNK, CREATING AN EXIT HAZARD AND A FIRE HAZARD |
CN194029 | Provide | 4609 RESTAURANT PROVIDE 3 HOUR SEPARATION BETWEEN GARAGE AND RESTAURANT (13-56-280) PROVIDE CLASS "A" FIRE DOOR BETWEEN GARAGE AND RESTAURANT |
CN194039 | Remove | 4603 OCCUPANCY CARD CALL FOR 39 OCCUPANCY 52 SEAT EXIST-REMOVE EXCESS SEATING (13-84-420) |
CN194039 | Remove | 4601 RESTAURANT REMOVE OTHER STORAGE ITEMS FROM FURNACE ROOM (7-28-060) |
CN197089 | Provide carbon monoxide detector for every 10,000 sq feet or less on every floor of Class C Assembly Unit. (13-64-190, 13-64-270) A carbon monoxide detector is needed whenever there is a heating appliance on the premises that burns fossil fuel such as gas, oil, or coal, or air that is circulated through a heat exchanger. Install according to manufacturer instructions. A hard wired model requires an electrical wiring permit. Every room containing a boiler requires a detector. Every floor with forced air heat, circulated air from a heat exchanger, or a fossil fuel burning appliance requires 1 detector for every 10,000 square feet or less. | 4601 RESTAURANT PROVIDE CARBON MONOXIDE DETECTOR |
CN198019 | File building registration statement with Building Dept. (13-10-030, 13-10-040) | REGISTER BUILDING FOR 2005 AND 2006 |
EL0023 | Install cover on outlet or junction box. (18-27-370.25) | INSTALL COVER ON ALL OPEN BOX |
EL0061 | Remove multiple conductor termination from device designed for single. (18-27-110.14(a), 18-27-110.14(b)) | REMOVE MULTIPLE CONDUCTOR TERMINATION FROM DEVICE DESIGNED FOR SINGLE |
EL0085 | PROPERLY PROTECT UNGROUNDED CONDUCTOR WITH PROPER SIZED OVER CURRENT DEVICE (18-27-215.2) | |
EL0091 | Obtain permit for electrical wiring and equipment installed without permit. (13-12-360) | INSTALLATION OF BOXES PANEL WIRE CONNECTION AND CONDUIT |
NC10012 | Enclose heating plant room by partitions, floor, and ceiling with at least 1 hour fire resistance. (15-8-220) | 4609 RESTAURANT ENCLOSE FURNACE ROOM 1 HOUR |
NC2011 | Performed or allowed work to be performed without submitting plans prepared, signed and sealed by a licensed architect or registered structural engineer for approval and without obtaining a permit to perform the work. (13-32-010, 13-32-040, 13-40-020, 13-12-050) | PROVIDE PLAN AND PERMIT FOR RESIDENTIAL INDIVIDUAL FURNACES |
NC2021 | Performed or allowed work to be performed erecting, enlarging, altering, repairing, removing or demolishing a building or part of a building without a permit. (13-12-050, 13-32-010, 13-32-130) | EVIDENCE OF PLUMBING REAPIRS AT MASONRY WALL AND AT FLOOR-PERMIT (?) |
NC3042 | Failed to provide and maintain uninterrupted means of egress to outside exit at grade level. (13-160-070, 13-160-100, 13-196-080) | 4609 RESTAURANT 50 SEATS REAR EXTERIOR DOOR OVER HEAD 4609 REAR VESTIBULE DOOR PADLOCK HARDWARE |
PL157037 | Repair or replace defective joints, connections, and fittings. (18-29-102.3) | (18-29-102.3) REPLACE ALL MISSING CLEAN OUT PLUGS WITH BRASS ONES |
PL161027 | Seal open drain from removal of plumbing fixture. (18-29-102.3) | (18-29-102.3) REMOVE ALL SOIL PIPE & FITTINGS THAT ARE NO LONGER IN USE |
PL171017 | Obtain permit for plumbing work before undertaking work. (18-29-106.1) | (18-29-106.1) PULL PERMIT |
PL171027 | Employ licensed and bonded plumber to perform plumbing work. (18-29-106.1 thru 106.2) | 1(4-32-010-100) HIRE LICENSED & BONDED PLUMBING CONTRACTOR |
PL231040 | Remove defective pipe, fitting, or fixture. (18-29-102.3) | (18-29-102.3) REMOVE ALL D.W.V. COPPER FROM WASTE & VENT LINES IN BASEMENT |
PL231040 | Remove defective pipe, fitting, or fixture. (18-29-102.3) | (18-29-102.3) REMOVE ALL DRESSLER COUPLINGS FROM ALL WASTE, VENTS & WATER LINES THROUGH OUT BUILDING |
PL232040 | Remove plumbing fixtures, water supply, soil, waste, and vent piping installed without permit. (13-12-050, 13-32-010) | (13-12-050,13-32-010),(18-29-105.4.) REMOVE ALL WASTE VENTS TRAPS & WATER PIPING INSTALLED WITHOUT PERMIT (IN BASEMENT RESTAURANTS) |
PL234032 | Install trap and/or waste and vent pipes. (18-29-906.1 thru 906.2), (18-29-1002.1) | (18-29-906.1-906.2),(18-29-100.1) PROVIDE PROPER WASTE, VENT & TRAP FOR WASHING MACHINE ON 3RD FLOOR |
PL235030 | Provide adequate support. (18-29-303.2), (18-29-308) | (18-29-303.2),(18-29-308) PROVIDE ADEQUATE HANGER FOR ALL PIPING |
PL235040 | Remove saddle hub and connections from house drain soil/waste vent pipe and install fittings. (18-29-707.1) | (18-29-707.1) REMOVE SADDLE HUB FITTING FROM WASTE LINE IN BASEMENT |
PL235050 | Protect plumbing system pipes from external corrosion. (18-29-305.1) | (18-29-305.1)PROTECT WATER & WASTE LINES FROM CORROSION CAN'T TOUCH OTHER PIPING OF DISSIMILAR METALS |
PL236020 | Install plumbing fixtures and equipment properly. (18-29-301.3) | (18-29-301.3) INSTALL EXPANSION TANKS ON ALL WATER HEATERS BASEMENT & RESTAURANTS |
PL237020 | Provide proper material for water supply pipe. (18-29-605) | (18-29-605) REPLACE OF GALVANIZING WATER PIPING THAT HAS ALREADY STARTED TO RUST DUE ELETORASIS |
PL237020 | Provide proper material for water supply pipe. (18-29-605) | (18-29-605) REMOVE ALL FLEXIBLE WATER SUPPLIES & REPLACE THEM WITH SOLID ONES |