The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.

Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.

The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.

ADDRESS: 1575 N MILWAUKEE AVE
Inspection # 14135616
VIOLATIONS BUILDING CODE CITATION VIOLATION DETAILS
CN031023 Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) FIRE EXTINGUISHERS NOT PROPERLY HUNG AT 1ST FLOOR
CN061014 Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) FRONT FACADE TILE AT GRADE- MISSING, LOOSE AND WASHED OUT MORTAR JOINTS.
EL1816 Install additional receptacle outlets. (14E-5-560.6, 14E-5-570.10(e)) ADD ADDITONAL RECEPTACLES THROUGH-OUT BUILDING TO EASE EXTENSION CORD USAGE
EL1817 Provide ground continuity for electrical cable, raceway, and enclosure. (14E-3-300.10, 14E-3-300.13) CONTINUITY OF RACEWAYS PROVIDE GROUNF CONTINUITY FOR CABLE, RACEWAYS (BSMT)
EL1818 Replace broken, inoperable, or painted over receptacle or switch. (14E-4-406.4) DEFECTIVE OUTLETS, REPLACE BROKEN, INOPEERABLE OR PAINTED OVER RECEPTACLES
EL1819 Replace defective light fixtures. (14E-4-410.20, 14E-4-410.21, 14E-4-410.22, 14E-4-410.23) REPLACE DEFECTIVE LIGHT FIXTURES (BSMT)REAR AREA EXPOSED LIVE WIRES
EL1822 Remove exposed wiring at light fixture. (14E-4-410.48) EXPOSED LIVE WIRES AT LIGHT FIXTURES THROUGH-OUT BUILDING
EL1827 Restore exit and emergency lighting system and related equipment to working condition. (14E-7-700.6) RESTORE EXITAND EMERGENCY LIGHTING SYSTEM AND RELATED EQUIPMENT TO WORKING CONDITION
EL1829 Remove exposed wiring. (14E-3-300.4) REMOVE ALL EXPOSE WIRE THROUGH-OUT BUILDING
EL1836 Provide detailed and legible panel schedules.(14E-4-408.4(a)) PROVIDE DETAILED AND LEGIBLE PANEL SCHEDULES
EL1837 Close unused opening in electrical box or cabinet. (14E-3-312.5(a)) CLOSE BOX OPENINGS THROUGH-OUT BUILDING
EL1840 Remove all abondoned raceways, cables, conductors, boxes and electrical equipment. 14E-1-110.1(c)) ABANDONED EQUIPMENT; REMOVE ALL ABANDONED RACEWAYS, CABLES CONDUCTORS' BOXES AND ELETRICAL EQUIPMENT
EL1853 Replace worn or defective conductor to pendant light fixture. (14E-4-410.54) REPLACE WORN DEFECTIVE CONDUCTOR TO PENDANT LIGHTING
EL1883 Repair emergency battery light unit. (14E-7-700.66) BOXES THROUGH-OUT NEE KO FILLERS
EL1886 OBTAIN ELECTRICAL PERMIT AND LICENSED ELECTRICIAN TO PERFORM WORK
NC6022 Failed to enclose public corridor in business, mercantile, industrial, storage unit, or building protected by sprinkler systems with partitions, floors and ceilings providing at least one hour fire resistance. (15-8-240) SEAL AND AND ALL PIPE PENETRTIONS IN BASEMENT CEILING.
PL170017 Provide floor drain with metallic strainer. (18-29-402.5) no floor drains in men and both women bathrooms at location
PL171017 Obtain permit for plumbing work before undertaking work. (18-29-106.1)
PL171027 Employ licensed and bonded plumber to perform plumbing work. (18-29-106.1 thru 106.2)
PL194029 Provide WATER MIXING VALVES AT ALL PUBLIC LAVATORIES THROUGHOUT LOCATION DANGEROUS AND HAZARDOUS 18.29.607.1.1
PL231040 Remove defective pipe, fitting, or fixture. (18-29-102.3) rubber tee fitting at three compartment sink at basement bar area
PL231040 Remove defective pipe, fitting, or fixture. (18-29-102.3) 2" rubber couplings that are used on the waste piping at the bars sinks and hand sinks in basement
PL232040 Remove plumbing fixtures, water supply, soil, waste, and vent piping installed without permit. (13-12-050, 13-32-010) remove plumbing fictures water supply and soil waste piping installed without permit and approved drawings
PL233016 Use proper size vent pipe and material for sump or receiving tank. (18-29-916.5) proper material for vent and waste pipe for sump or recieving tank /pit located in commerical liquor room dangerous and hazardous
PL234002 Provide proper soil/waste vent pipe material. (18-29-702) pvc and plastic hose used for waste pipe at all three bar locations, kitchen area, and lavatories waste throughout location dangerous and hazardous
PL234018 Install vent pipe for trap. (18-29-901.2 thru 18-29-901.2.1) no vents for p-traps at all bars and kitchen sinks, hand sinks throughout location dangerous and hazardous
PL234030 Install indirect clear water waste pipe. (18-29-802.1.3), (18-29-802.1.4) hose drilled into 4" pvc waste in basement near kithen area dangerous and hazardous
PL236040 Provide non-absorbent open-front toilet seat for employees or public.(18-29-420.3) no open front toilet seats installed on commerical toilets throughout location
PL237004 Provide indirect connection for water supply. (18-29-602), (18-29-608) no inline backflow valve on ice machine dangerous and hazardous
PL237004 Provide indirect connection for water supply. (18-29-602), (18-29-608) NO RPZ FOR SODA DRINK MACHINE STATIONS THROUHGOUT LOCATION DANGEROUS AND HAZARDOUS
PL237014 Provide ball cock, vacuum breaker, or air gap. (18-29-606.5.6) no vacuum breaker at mop sink faucet by ice machine dangerous and hazardous
PL237026 Provide water supply pipe with air chambers. (18-29-604.11), (18-29-604.11.1) NO AIR CHAMBERS OR AIR ARESTORS THROUGHOUT LOCATION FOR POTABLE WATER SYSTEM