The information presented on this website is informational only and does not necessarily reflect the current condition of the building or property. The fact that a permit was issued does not confirm that work was performed, or that work was performed in accordance with that permit and the requirements of the Municipal Code.
Information on inspections and alleged violations reflect conditions found by the inspector at the time of the inspection and not necessarily the current status of those alleged violations or the current condition of the property. The absence of alleged violations on this website does not mean a building or property is in compliance with the requirements of the Municipal Code.
The Department of Buildings may refer certain alleged violations to the City's Department of Law for enforcement proceedings in the Department of Administrative Hearings or the Circuit Court of Cook County. Please contact the Department of Administrative Hearings or the Clerk of the Circuit Court, respectively to obtain records of these proceedings.
| Inspection # 14135616 | ||
|---|---|---|
| VIOLATIONS | BUILDING CODE CITATION | VIOLATION DETAILS |
| CN031023 | Failed to maintain properly charged fire extinguisher and to attach tag which clearly indicates recharge date and signature of the person who performed the recharge. (15-16-680) | FIRE EXTINGUISHERS NOT PROPERLY HUNG AT 1ST FLOOR |
| CN061014 | Failed to maintain the exterior walls of a building or structure free from holes, breaks, loose or rotting boards or timbers and any other conditions which might admit rain or dampness to the walls. (13-196-530(b), 13-196-641) | FRONT FACADE TILE AT GRADE- MISSING, LOOSE AND WASHED OUT MORTAR JOINTS. |
| EL1816 | Install additional receptacle outlets. (14E-5-560.6, 14E-5-570.10(e)) | ADD ADDITONAL RECEPTACLES THROUGH-OUT BUILDING TO EASE EXTENSION CORD USAGE |
| EL1817 | Provide ground continuity for electrical cable, raceway, and enclosure. (14E-3-300.10, 14E-3-300.13) | CONTINUITY OF RACEWAYS PROVIDE GROUNF CONTINUITY FOR CABLE, RACEWAYS (BSMT) |
| EL1818 | Replace broken, inoperable, or painted over receptacle or switch. (14E-4-406.4) | DEFECTIVE OUTLETS, REPLACE BROKEN, INOPEERABLE OR PAINTED OVER RECEPTACLES |
| EL1819 | Replace defective light fixtures. (14E-4-410.20, 14E-4-410.21, 14E-4-410.22, 14E-4-410.23) | REPLACE DEFECTIVE LIGHT FIXTURES (BSMT)REAR AREA EXPOSED LIVE WIRES |
| EL1822 | Remove exposed wiring at light fixture. (14E-4-410.48) | EXPOSED LIVE WIRES AT LIGHT FIXTURES THROUGH-OUT BUILDING |
| EL1827 | Restore exit and emergency lighting system and related equipment to working condition. (14E-7-700.6) | RESTORE EXITAND EMERGENCY LIGHTING SYSTEM AND RELATED EQUIPMENT TO WORKING CONDITION |
| EL1829 | Remove exposed wiring. (14E-3-300.4) | REMOVE ALL EXPOSE WIRE THROUGH-OUT BUILDING |
| EL1836 | Provide detailed and legible panel schedules.(14E-4-408.4(a)) | PROVIDE DETAILED AND LEGIBLE PANEL SCHEDULES |
| EL1837 | Close unused opening in electrical box or cabinet. (14E-3-312.5(a)) | CLOSE BOX OPENINGS THROUGH-OUT BUILDING |
| EL1840 | Remove all abondoned raceways, cables, conductors, boxes and electrical equipment. 14E-1-110.1(c)) | ABANDONED EQUIPMENT; REMOVE ALL ABANDONED RACEWAYS, CABLES CONDUCTORS' BOXES AND ELETRICAL EQUIPMENT |
| EL1853 | Replace worn or defective conductor to pendant light fixture. (14E-4-410.54) | REPLACE WORN DEFECTIVE CONDUCTOR TO PENDANT LIGHTING |
| EL1883 | Repair emergency battery light unit. (14E-7-700.66) | BOXES THROUGH-OUT NEE KO FILLERS |
| EL1886 | OBTAIN ELECTRICAL PERMIT AND LICENSED ELECTRICIAN TO PERFORM WORK | |
| NC6022 | Failed to enclose public corridor in business, mercantile, industrial, storage unit, or building protected by sprinkler systems with partitions, floors and ceilings providing at least one hour fire resistance. (15-8-240) | SEAL AND AND ALL PIPE PENETRTIONS IN BASEMENT CEILING. |
| PL170017 | Provide floor drain with metallic strainer. (18-29-402.5) | no floor drains in men and both women bathrooms at location |
| PL171017 | Obtain permit for plumbing work before undertaking work. (18-29-106.1) | |
| PL171027 | Employ licensed and bonded plumber to perform plumbing work. (18-29-106.1 thru 106.2) | |
| PL194029 | Provide | WATER MIXING VALVES AT ALL PUBLIC LAVATORIES THROUGHOUT LOCATION DANGEROUS AND HAZARDOUS 18.29.607.1.1 |
| PL231040 | Remove defective pipe, fitting, or fixture. (18-29-102.3) | rubber tee fitting at three compartment sink at basement bar area |
| PL231040 | Remove defective pipe, fitting, or fixture. (18-29-102.3) | 2" rubber couplings that are used on the waste piping at the bars sinks and hand sinks in basement |
| PL232040 | Remove plumbing fixtures, water supply, soil, waste, and vent piping installed without permit. (13-12-050, 13-32-010) | remove plumbing fictures water supply and soil waste piping installed without permit and approved drawings |
| PL233016 | Use proper size vent pipe and material for sump or receiving tank. (18-29-916.5) | proper material for vent and waste pipe for sump or recieving tank /pit located in commerical liquor room dangerous and hazardous |
| PL234002 | Provide proper soil/waste vent pipe material. (18-29-702) | pvc and plastic hose used for waste pipe at all three bar locations, kitchen area, and lavatories waste throughout location dangerous and hazardous |
| PL234018 | Install vent pipe for trap. (18-29-901.2 thru 18-29-901.2.1) | no vents for p-traps at all bars and kitchen sinks, hand sinks throughout location dangerous and hazardous |
| PL234030 | Install indirect clear water waste pipe. (18-29-802.1.3), (18-29-802.1.4) | hose drilled into 4" pvc waste in basement near kithen area dangerous and hazardous |
| PL236040 | Provide non-absorbent open-front toilet seat for employees or public.(18-29-420.3) | no open front toilet seats installed on commerical toilets throughout location |
| PL237004 | Provide indirect connection for water supply. (18-29-602), (18-29-608) | no inline backflow valve on ice machine dangerous and hazardous |
| PL237004 | Provide indirect connection for water supply. (18-29-602), (18-29-608) | NO RPZ FOR SODA DRINK MACHINE STATIONS THROUHGOUT LOCATION DANGEROUS AND HAZARDOUS |
| PL237014 | Provide ball cock, vacuum breaker, or air gap. (18-29-606.5.6) | no vacuum breaker at mop sink faucet by ice machine dangerous and hazardous |
| PL237026 | Provide water supply pipe with air chambers. (18-29-604.11), (18-29-604.11.1) | NO AIR CHAMBERS OR AIR ARESTORS THROUGHOUT LOCATION FOR POTABLE WATER SYSTEM |